YVZ3V-R (NYFGby)


















Application: Underground, indoor and outdoor installation, where better mechanical protection or higher is required

resistance to higher tensile stress is required.

Technical data: There is an armour of galvanized flat steel wires between inner covering and outer sheath

against mechanical stresses.

Max. conductor temperature: 70°C

Rated voltage: 0.6/1kV











Rated Number of Conductor Insulation Outer Sheath Outer Resistance Rated Current Weight
Crosssection Strands Diameter Thickness Thickness Diameter at 20 °C Ground Air approx.
(mm²)
(mm) (mm) (mm) (mm) (mΩ/m)

(kg/km)
3x25+16 7 6.4 1.2 2 28 0.727 130 105 2200
3x35+16 7-19 7.7 1.2 2 31 0.524 155 130 2700
3x50+25 19 9.2 1.4 2.2 35 0.387 185 160 3680
3x70+35 19 11 1.4 2.2 41 0.268 230 200 4550
3x95+50 19 12.7 1.6 2.6 47.5 0.193 275 245 6000
3x120+70 37 14.4 1.6 2.6 51 0.153 315 285 7000
3x150+70 37 16.1 1.8 2.6 55 0.124 355 325 8500
3x185+95 37 18 2.0 3 62 0.0991 400 370 10050
3x240+120 61 20.5 2.2 3.4 69 0.0754 465 435 12850
4x10 1 3.6 1.0 1.8 21.5 1.83 77 60 1210
4x16 7 5.1 1.0 2 26 1.15 100 80 1700
4x25 7 6.4 1.2 2 30 0.727 130 105 2075
4x35 7-19 7.7 1.2 2 33 0.524 155 130 2400
4x50 19 9.2 1.4 2.2 38 0.387 185 160 3130