| NYM | |||||||
| Application: In dry, damp and wet locations on premises and in store rooms with fire and explosion hazard. | |||||||
| Can be used outdoors but cannot be buried underground. | |||||||
| Techinical data: 1.5mm2 – 10mm2 are single-core, 10 and 16mm2 are multi-core. Insulation is TI 1 thermoplastic. | |||||||
| Twisted. Outer sheath color is grey. | |||||||
| Max. conductor temperature: 70°C | |||||||
| Rated voltage: 300/500V | |||||||
| Rated | Number of | Conductor | Insulation | Outer Sheath | Outer | Weight | Resistance |
| Crosssection | Strands | Diameter | Thickness | Thickness | Diameter | approx. | at 20 °C |
| (mm²) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (mΩ/m) | |
| 2x1.5 | 1 | 1.38 | 0.6 | 1.4 | 8 | 116 | 12.1 |
| 2x2.5 | 1 | 1.80 | 0.7 | 1.4 | 10 | 160 | 7.28 |
| 2x4 | 1 | 2.26 | 0.8 | 1.4 | 11.4 | 218 | 4.56 |
| 2x6 | 1 | 2.80 | 0.7 | 1.4 | 12.4 | 277 | 3.03 |
| 2x10 | 1-7 | 4.10 | 1.0 | 1.6 | 16.4 | 488 | 1.83 |
| 2x16 | 1-7 | 5.20 | 1.0 | 1.6 | 18.6 | 600 | 1.15 |
| 3x1.5 | 1 | 1.38 | 0.6 | 1.4 | 9.2 | 136 | 12.1 |
| 3x2.5 | 1 | 1.80 | 0.7 | 1.4 | 10.5 | 189 | 7.28 |
| 3x4 | 1 | 2.26 | 0.8 | 1.4 | 12 | 262 | 4.56 |
| 3x6 | 1 | 2.80 | 0.8 | 1.6 | 13.5 | 353 | 3.03 |
| 3x10 | 1-7 | 4.10 | 1.0 | 1.6 | 17.4 | 601 | 1.83 |
| 3x16 | 1-7 | 5.20 | 1.0 | 1.6 | 20 | 856 | 1.15 |
| 4x1.5 | 1 | 1.38 | 0.6 | 1.4 | 10 | 163 | 12.1 |
| 4x2.5 | 1 | 1.80 | 0.7 | 1.4 | 11.3 | 231 | 7.28 |
| 4x4 | 1 | 2.26 | 0.8 | 1.6 | 13.4 | 236 | 4.56 |
| 4x6 | 1 | 2.80 | 0.8 | 1.6 | 15 | 452 | 3.03 |
| 4x10 | 1-7 | 4.10 | 1.1 | 1.6 | 19 | 746 | 1.83 |
| 4x16 | 1-7 | 5.20 | 1.0 | 1.6 | 22 | 1071 | 1.15 |